YXZ2V-U, YXZ2V-R, N2XRY

Place of use

These cables have a low dielectric loss, used in indoors and outdoors, in cable ducts, underground, in power or switching stations, local energy distributions, industrial plants, where there is risk of mechanical damage. 

Structure

1. Solid or stranded copper conductor.
2. XLPE insulation.
3. Filler.
4. Galvanized round steel wires.
5. Polyester tape.
6. PVC outer sheath. 

Product Code Dimension and Weights Electrical Properties
Nominal Cross Section Overall Diemeter
( ~ )
Net Weight
( ~ )
Standart Lenght Max. Dc Conductor Resistance at 20◦ C Current Carrying Capacity
In Ground at 20° C On Air at 30° C
c 4x1.5 14.0 380 1000 12.1 30 24
28-47000002 4x2.5 15.0 440 1000 7.41 40 32
28-47000003 4x4 16.0 550 1000 4.61 52 42
28-47000004 4x6 18.5 800 1000 3.08 64 53
28-47000005 4x10 21.0 1100 1000 1.83 86 73
28-47000006 4x16 24.0 1550 1000 1.15 111 96
28-47000007 4x25 28.0 2150 1000 0.727 143 130
28-47000008 4x35 30.5 2700 1000 0.524 173 160
28-47000009 4x50 34.0 3400 1000 0.387 205 195
28-47000010 4x70 40.0 4850 1000 0.268 252 247
28-47000011 4x95 44.0 6150 500 0.193 303 305
28-47000012 4x120 50.5 8000 500 0.153 346 355

Technical Info

Catalog Info